Quantum G6 / G7 Diagnostic tool

8. Power Issues

.

Product Dead

Note this is VERY rare, especially “out of the box” as each heater is tested at the end of the factory line.





Cause :

• No peak supply present.


Remedy :

  • Check both isolation switches on wall switched ON.
  •  Check fuse in wall switch is OK. 


  • Check all MCBs are switched ON. 
  • Check cable terminations in fuse spur and on heater terminal block.

Cause:

Peak & off-peak supplies swapped wrong way around by installer? 


Remedy:

Symptoms will be display only works at night when off-peak supply energises.  Swap peak & off-peak cables round the correct way.


Cause:

• Switch on wall faulty. 

Remedy:

  • Customer to replace 
  • Replace switch from van stock / pick one up from wholesaler & fit as goodwill gesture. After all, customer may have been without heat for a while.


Cause:

• Screen accidentally unplugged from Charge Controller whilst installing. 

Remedy:

  • Installer to check UI cable is correctly connected to CC board. 


Cause:

Fault with UI screen or Charge Controller.


Remedy:

Change UI & power on heater. If UI still dead, isolate mains. Check all connections to CC PCB. If suspected faulty, take photo of PCB then replace. PHOTO DATA BADGE FOR REPORT.